Fire-proof Materials for Construction of Clean Operating Room
Release time:2019-08-07 source:
In addition to the high requirement for cleanliness, clean operating room should also have higher safety for fire protection performance of materials, so it is necessary to prevent life hazards in the future. The following suggestions for fire prevention in clean operating room are put forward by Ed Purification Branch
1. The clean operation department shall be located in a building whose fire resistance level is not lower than the second level.
2 Clean operation department should be divided into separate fire prevention zones. Effective fire and smoke prevention should be adopted when it is in the same fire prevention zone as other parts.
Separation measures shall be taken, and the partition wall with a fire resistance limit not less than 2.00h shall be separated from other parts; the door connecting the area of the non-clean operation department shall be adopted.
Fire-proof doors with fire-proof limits not less than Class B (except those directly accessing open outer corridors or directly outside doors), or other corresponding fire-proof technologies
Measures.
3. Fire and smoke prevention measures should be taken in the links between the technical interlayer of the clean operating department and the operating room and auxiliary room, and the fire-resistant pole of the separator should be used.
The limit should not be less than 1.00h.
Clean Operating Room Construction Personnel
When indoor fire hydrant is needed, it is not necessary to install fire hydrant in the operating room, but fire hydrant outside the operating room should ensure two water guns.
When no fire hydrant is needed in the clean operating room, fire hose reels should be set up to extinguish.
Fire facilities. When automatic sprinkler fire extinguishing system is needed, sprinklers should not be arranged in the operating room. Building fire extinguishing should be set up in clean operation Department
Device.
5 The automatic fire alarm device should be installed in the technical interlayer of the clean operation department.
6 The clean operation department shall design the smoke control and exhaust system for windowless buildings or windowless rooms in buildings according to the relevant building fire protection codes.
7 There should be anti-backfilling measures at the smoke outlet in the clean area. Plate type smoke outlet must be used in smoke outlet.
The smoke exhaust valves in the clean area should be installed in an embedded way. The surface of the smoke exhaust valves should be easy to clean and disinfect.
***** Pay special attention to:
A device that can cut off the central oxygen supply pipe urgently should be installed in the clean operation department.
The professional technicians of Ed Purification Engineering design a reasonable plan to adapt to the production process and the cost of the project. The design technical indicators meet the national standard of clean room. The experienced construction team of the purification project is fast and efficient, and the after-sales service is perfect.