Operation room purification air conditioning unit commissioning precautions
Release time:2020-01-20 source:
Operation room purification air conditioning unit commissioning precautions
① Wiring shall be conducted in strict accordance with the unit circuit diagram, and safety inspection shall be conducted for the electrical circuit diagram before startup. The insulation resistance of the motor to the ground is greater than 2m Ω, the current of the exposed metal and power line is less than 1.5mA, and the resistance between the exposed metal part and the grounding terminal is not greater than 4 Ω.
② Check whether the air valve in the air duct is open, so as to avoid subjective judgment error during commissioning.
③ When the fan is used for the first time, check whether the rotation direction of the fan is correct. The air volume ratio when the fan is reversed is obviously smaller than that when the fan is rotating forward. For example, reverse the electric wire position of the two phases.
④ After the normal operation of the water circuit, open the vent valve on the water pipe of the heat exchanger and close it after the air is drained.
⑤ When the unit is running, the system shall be adjusted reasonably to control the water temperature difference and running current within the specified value
⑥ Do not remove the wall panel when the unit is running.
⑦ The freezing water temperature of the unit in summer shall not be less than 4 ℃, the hot water temperature in winter shall not be more than 65 ℃, and the water temperature shall be more than 80 ℃. The press out form can be used. The hot and cold water shall be softened. The water pressure is not more than 16KG / cm2
⑧ The heat exchanger of the unit shall be filled with water during the non service period to reduce the corrosion of copper pipes. In winter, the water in the heat exchanger must be drained to avoid freezing and damaging the heat exchanger, and at the same time, the circulation with the outside air must be cut off
Shandong ed purification Engineering Co., Ltd. is mainly engaged in the design and installation of air purification projects, mainly including: operating room purification, ICU purification engineering, electronic workshop, workshop purification engineering, suspension bridge crane tower, and has perfect pre-sales and after-sales services. All employees of the company, in the spirit of cooperation, due diligence and active development, with the support of all sectors of the society, have embarked on a path of enterprise growth of "quality for survival, management for efficiency". For more knowledge of clean room purification industry, please pay attention to WeChat public address: Aide-188 (Ed purified oxygen supply).